Energy-Efficient Wood Wall Assemblies
Design professionals face many decisions and options when choosing design approaches and materials that meet today’s more stringent energy codes for light commercial and multifamily construction. The variety of primary construction materials that can be specified differ between regions and cities based on climate zone, product availability, and historical preferences. As the energy codes have become more stringent, the insulation requirements for different climate zones can also influence changes in how exterior walls are constructed. Because construction materials can vary greatly in terms of energy performance, it is increasingly important to recognize the thermal performance characteristics of the specified products in project design.
Wood naturally has a higher thermal resistance compared to steel or masonry, making it a superior product for improving energy efficiency when used in wall assemblies. Wood studs have nearly four times the thermal resistance of steel studs or masonry blocks: A nominal 2x4 stud has an R-value of 4.38, whereas a 3-1/2” cold rolled steel stud has an R-value of 1.34, and an 8-inch nominal concrete masonry unit (CMU) has an R-value of 1.11. The 2015 International Energy Conservation Code (IECC) recognizes this difference and requires continuous insulation on steel and CMU wall assemblies.
Some erroneously assume that the use of steel and concrete masonry wall systems with continuous insulation (c.i.) provides a wall superior in energy efficiency to wood framed construction without continuous insulation. This assumption is based on a misconception that continuous insulation mitigates the insulating deficiencies of steel framing and CMU walls by neutralizing the significant thermal bridging in non-wood structures.
APA put this assumption to the test through an energy-efficiency analysis which compared steel framing and masonry block wall assemblies that use continuous insulation with wood-framed wall construction without continuous insulation.
The Analysis
The purpose of this analysis is to determine the impact of three wall assembly types on the annual cost [1] of energy consumption [2] in the three different climate zones. Table 1 shows the three systems based on Group R occupancies for multifamily buildings in climate zones 3, 4 and 5. Three types of wall construction systems were selected from Table C402.1.3 of the 2015 IECC, and each system was evaluated for each climate zone. The design parameters are identical except for the type of wall system. The evaluation was done using RemDesign software, a nationally recognized tool for calculating the energy consumption of residential building designs, and is based on a 28,500 square-foot multifamily building with 256,500 cubic-foot of volume consisting of 27 individual units with 57 bedrooms.
Table 1
Above Grade Wall Systems |
CMU [a] |
Metal Framed [b] |
Wood Framed [c] |
Climate Zone 3 – R |
Block + R-9.5 c.i. |
R-13 + R-7.5 c.i. |
R-20 |
Climate Zone 4 – R |
Block + R-11.4 c.i. |
R-13 + R-7.5 c.i. |
R-20 |
Climate Zone 5 – R |
Block + R-13.3 c.i. |
R-13 + R-7.5 c.i. |
R-20 + R-3.8 c.i. |
a. CMU wall defined as 8” nominal CMU without core fill insulation, and using continuous insulation (c.i.) as defined above. Component U-values for 9.5, 11.4, and 13.3 continuous insulation are 0.0908, 0.0774, and 0.0675, respectively.
b. Metal framed walls assume 3-1/2” nominal steel stud 16” o.c. with R-7.5 c.i. installed on the exterior surface. Component u-value of 0.059.
c. Wood framed walls assume 2x6 exterior wall studs, 16” o.c. component U value of .060, with c.i. installed as required above. |
In climate zone 3, the annual cost for energy consumption of the buildings with the wood-framed walls was $1317.24. The cost of energy for the steel-framed and the CMU walls was $1308.03 and $1307.40, respectively. The results indicate that the wall systems, as listed in the IECC, have similar levels of performance in terms of energy efficiency in relatively warmer climates.
In climate zone 4, the wood-framed, steel-framed and CMU walls result in an annual energy consumption cost of $1,030.14, $1,019.70, and $980.33, respectively. In this climate zone, wood-framed walls and steel-framed walls utilize almost the same amount of energy, while CMU walls with a thicker c.i. requirement perform slightly better.
In climate zone 5, the annual energy consumption costs are $831.18, $978.65, and $912.65 for wood, steel, and CMU, respectively. In this climate zone, the wood-framed walls are required to have continuous insulation with a minimum R-value of 3.8 installed on the exterior. As a result, the wood framed walls reduce annual energy consumption by 18 percent compared to steel framing and by 10 percent compared to CMU walls. The benefits of using wood-framed wall assemblies become more apparent in increasingly colder climates [3].